CLAMP-ON GROUND RESISTANCE METER

( ground resistance clamp on meter, ground resistance clamp-on meter, clamp-on ground resistance meter, clamp on ground resistance meter, earth resistance clamp on meter, earth resistance clamp-on meter, clamp on earth resistance meter, clamp-on earth resistance meter, Digital Clamp On Meter, Digital Clamp-On Meter, Digital Clamp Multimeter )

XHST2000 (jaw size: 65*32mm)                                                                  XHST2100 (jaw size: dia.32mm) basic model

Earth Resistance Tester XHST 2000/2100
CE


XHST 2000/2100 of Pincer Earth Tester, in the measurement of a grounding system with loop current,does not require breaking down the grounding wire, and need no auxiliary electrode. It is safe, fast and simple in use.

XHST 2000
• In According with GB/T 1.1-2000
• Safe,Fast response and Simple in use

1 Liquid Crystal Display (LCD)
2 Trigger: to control opening and closing of jaw :
3 Pincer Jaw : 65 x 32mm
4 POWER Key: Boot Up / Shutdown / * Quit
5 HOLD Key: lock / Release display
Technical Specifications
Power Source 6VDC (4 ℅5# alkaline battery)
Working Temperature -10 ∼ -55 ∼ C
Relative Humidity 10%-90%
LCD 4-digital LCD, 47 ℅ 28.5mm in length
Span of Jaw 28mm
Net weight 1160g
Demension(mm) 285* 85 * 56
Protection Level Double insulation
Structural Feature In the jaw way
Shift Automatic
External Magnetic Field ˉ 40A/m
External Electric Field ˉ 1V/m
Measuring Time 1 second
Resistance Measurement Frequency ˇ 1KHz
Maximum Resistance Measurement Resolution 0.001 次
Range of Resistence Measurement 0.01-1000 次
Accessories Carry Case(1),Strap(1), 5# Alkaline Battery

Survey pattern
survey scope
resolving power
accuracy
Resistance
0.010~0.099ㄗ次ㄘ
0.001ㄗ次ㄘ
㊣(1ㄔ+0.01次)
0.10~0.99ㄗ次ㄘ
0.01ㄗ次ㄘ
㊣(1ㄔ+0.01次)
1.0~49.9ㄗ次ㄘ
0.1ㄗ次ㄘ
㊣(1.5ㄔ+0.1次)
50.0~99.5ㄗ次ㄘ
0.5ㄗ次ㄘ
㊣(3ㄔ+0.5次)
100~199ㄗ次ㄘ
1ㄗ次ㄘ
㊣(3ㄔ+1次)
200~395ㄗ次ㄘ
5ㄗ次ㄘ
㊣(6ㄔ+5次)
400~590ㄗ次ㄘ
10ㄗ次ㄘ
㊣(10ㄔ+10次)
600~1000ㄗ次ㄘ
20ㄗ次ㄘ
㊣(20ㄔ+20次)
     

XHST2000A (jaw size: 65*32mm)          practical model

Earth Resistance Tester XHST 2000A
CE

XHST 2000A of Pincer Earth Tester, in the measurement of a grounding system with loop,does not require breaking down the grounding wire, and need no auxiliary electrode. It is safe, fast and simple in use.


XHST 2000A
 
• In According with GB/T 1.1-2000
• Safe,Fast response and Simple in use

1 Liquid Crystal Display (LCD)
2 Trigger: to control opening and closing of jaw 3 Pincer Jaw : 65 x 32mm
4 POWER Key: Boot Up / Shutdown/ * Quit
5 HOLD Key: lock / Release display
Technical Specifications
Power Source 6VDC (4 ℅5# alkaline battery)
Working Temperature -10 ∼ -55 ∼ C
Relative Humidity 10%-90%
LCD 4-digital LCD, 47 ℅ 28.5mm in length
Span of Jaw 28mm
Net weight 1160g
Demension(mm) 285* 85 * 56
Protection Level Double insulation
Structural Feature In the jaw way
Shift Automatic
External Magnetic Field ˉ 40A/m
External Electric Field ˉ 1V/m
Measuring Time 1 second
Resistance Measurement Frequency ˇ 1KHz
Maximum Resistance Measurement Resolution 0.001 次
Range of Resistence Measurement 0.01-200 次
Accessories Carry Case(1),Strap(1), 5# Alkaline Battery

Survey pattern
survey scope
resolving power
accuracy
Resistance
0.010~0.099ㄗ次ㄘ
0.001ㄗ次ㄘ
㊣(1ㄔ+0.01次)
0.10~0.99ㄗ次ㄘ
0.01ㄗ次ㄘ
㊣(1ㄔ+0.01次)
1.0~49.9ㄗ次ㄘ
0.1ㄗ次ㄘ
㊣(1.5ㄔ+0.1次)
50.0~99.5ㄗ次ㄘ
0.5ㄗ次ㄘ
㊣(2ㄔ+0.5次)
100~199ㄗ次ㄘ
1ㄗ次ㄘ
㊣(3ㄔ+1次)
200~395ㄗ次ㄘ
5ㄗ次ㄘ
㊣(6ㄔ+5次)
400~590ㄗ次ㄘ
10ㄗ次ㄘ
㊣(10ㄔ+10次)
600~1000ㄗ次ㄘ
20ㄗ次ㄘ
㊣(20ㄔ+20次)
 
     

       

XHST2000C (jaw size: 65*32mm)                    XHST2100C (jaw size: dia.32mm)

multifunctional model (with data keeping, alarm)

Earth Resistance Tester XHST 2000C/2100C
CE

XHST 2000C/2100C of Pincer Earth Tester, in the measurement of a grounding system with loop current,does not require breaking down the grounding wire, and need no auxiliary electrode. It ia also able to measure the leakage current and the neutral current in the grounding system. It is safe, fast and simple in use.


XHST 2000C
 
• In According with GB/T 1.1-2000
• Safe,Fast response and Simple in use

1. Liquid Crystal Display (LCD)
2. Trigger: to control opening and closing of jaw 3 .Pincer Jaw : 65 x 32mm
4 .POWER Key: Boot Up / Shutdown/ * Quit
5 .MODE Key : switch key of function mode (resistance measurement / current measurement /data access)
6. SET Key : function key combinations (Combination with MODE key to achieve: Lock / Release / Storage / Set / Check / Browse / Delete Data)
Technical Specifications
Power Source 6VDC (4 ℅5# alkaline battery)
Working Temperature -10 ∼ -55 ∼ C
Relative Humidity 10%-90%
LCD 4-digital LCD, 47 ℅ 28.5mm in length
Span of Jaw 28mm
Net weight 1160g
Demension(mm) 285* 85 * 56
Protection Level Double insulation
Structural Feature In the jaw way
Shift Automatic
External Magnetic Field ˉ 40A/m
External Electric Field ˉ 1V/m
Measuring Time 1 second
Resistance Measurement Frequency ˇ 1KHz
Maximum Resistance Measurement Resolution 0.001 次
Range of Resistence Measurement 0.01-1000 次
Current Measurement Range 0.00 -20.0A
Current Measurement Frequency 45-65Hz
Storable Measurement Data 50 Units
Setting Range of Resistance Alarm Critical Value 1-199 次
Setting Range of Current Alarm Critical Value 1-499mA
Accessories Carry Case(1),Strap(1), 5# Alkaline Battery

Survey pattern
survey scope
resolving power
accuracy
Resistance
0.010~0.099ㄗ次ㄘ
0.001ㄗ次ㄘ
㊣(1ㄔ+0.01次)
0.10~0.99ㄗ次ㄘ
0.01ㄗ次ㄘ
㊣(1ㄔ+0.01次)
1.0~49.9ㄗ次ㄘ
0.1ㄗ次ㄘ
㊣(1.5ㄔ+0.1次)
50.0~99.5ㄗ次ㄘ
0.5ㄗ次ㄘ
㊣(2ㄔ+0.5次)
100~199ㄗ次ㄘ
1ㄗ次ㄘ
㊣(3ㄔ+1次)
200~395ㄗ次ㄘ
5ㄗ次ㄘ
㊣(6ㄔ+5次)
400~590ㄗ次ㄘ
10ㄗ次ㄘ
㊣(10ㄔ+10次)
600~1000ㄗ次ㄘ
20ㄗ次ㄘ
㊣(20ㄔ+20次)
Electric current
0.00~299 mA
1 mA
㊣(5ㄔ+2 mA)
100~299 mA 1 mA ㊣(5ㄔ+5 mA)
0.30~2.99 A
10 mA
㊣(5ㄔ+0.03 mA)
3.00~9.99 A 10 mA ㊣(5ㄔ+0.4 mA)
10.00~20.00 A
10 mA
㊣(5ㄔ+0.5 mA)
 
     

 ( If you need user manual or E-catalogue for above meters, please ask for at: xiushunjie@gmail.com )